How can power be recovered from a T-dam: (Gp : Gross
Power)
Power can be harvested from a T-dam using a wide variety of
methods.
The easiest method to describe is to harvest power via torsional
rotation. This is accomplished by inserting 1 or more
paddle wheels in the descent path, to intercept the saturated rotors as
they fall. The axis of the paddle wheel is attached to a
standard generator. A differential, and flywheel may be
necessary, as required by the particular generator. In this method
the rotors are not required to hold a magnetic charge and can therefore
be shelled with some sort of high impact plastic. As more rotors
are introduced into the circulation, the number of simultaneous impact,
limited only by the design of the system, will increase the torsional
output on the paddle wheel. This method can also be used to
compress gases or as a propulsion method.
The most efficient method is via direct magnetic induction.
As the magnetizable rotors fall through the ascent channel, they fall
through the center of one or more strong magnetic fields. As the
magnetic field violently clash, current is induced and stored in an
attached battery. Normalization of the charges via rectification, or
other methods will be required.
Energy in the form of continuous impacts can be captured at
one or more points in the descent channel. This is accomplished by
an intervening surface, which captures the impacts, and then allows the
rotors to continue their cycle.
|
|
How can the net power out be more than the inputs: (Np
: Net Power)
The source of energy from any system, is a relative term.
In hydro-electric power, the medium is water, but the "source of power"
is gravity. A traditional hydro-electric dam, uses the negative
buoyancy of water (free-fall) in atmosphere to convert an apparently
unlimited gravitational force into torsional rotation. A T-dam
uses the positive buoyancy of trapped gas (free-float) in fluid, to
convert the same unlimited gravitational force into torsional rotation.
Additionally, a T-dam can more directly convert this gravitational force
into electricity via magnetic induction.
Therefore in that it can be accepted that flotation
(free-float) is the opposite of falling (free-fall), and that both are
the results of gravitational forces tapped from the interaction of
materials of significantly different densities, within a gravitational
field.. The question of sources of energy of a T-dam are completely
answered.
In short, that question does not apply to a T-dam.
The idea that energy is some commodity that must be moved about is
inaccurate.
In a traditional electric generator, powered by fossil fuels.
The electrical force is tapped by the generator, it is not
created. To say that a standard generator creates electricity,
is analogous to saying that the Dutch boy removed his finger from a
small hole in the dike, did so with enough force to generates the flood
that followed. In both cases the actions of the generator and the
boy, are methods of enabling or organizing the flow a vast potential
resource.
Both solar and wind power can easily be traced to similar tapping
methods.
_ _ _
The trick dam is so called because just as the magician uses a small
amount of energy, in a diversion, or furtive movement to achieve the
greater goal of the illusion. A trick dam can generate a
substantial power output via torsional rotation, direct magnetic
induction, or continuous impact capture. Each of these methods is
scalable. This means that by using more effective (larger) rotors,
denser fluid, longer or more numerous channels the power potentials can
be optimized.
The required power inputs, depend upon the implementation, i.e. lake
or river application, standalone, or municipal designs. The most power
hungry of these designs is the closed standalone
design. The power inputs for this design are;
Upper impeller (UIp):
The impeller is required to lift multiple floated rotors, from the
top of the ascent channel, and deposit them into the top of the descent
channel(s). The maximum distance of travel will be
roughly 1/2 of the outer circumference of the impeller. This
distance will be determined by the configuration of the channels.
The rotor size, rotors saturated weight, and the operational speed of
the impeller will determine the power requirements. The
paddles of the impeller will be vented to allow excess fluid to
immediately drain back into the top of the ascent channel, however the
weight of some residual fluid will add to the power burden of this
component. The final power requirement is that required to
move the impeller paddles through the fluid itself. However,
since this is a given range, from 0-max capacity, this power requirement
can be compensated by increasing Gp.
A couple of notes are important here. In the lake (still
water design) this is a minimal power drain, and in the river (moving
water design) this may required substantially more power, plus the
power needed to pump water up to the saturation platform.
Also, if very buoyant rotors, in sufficient number the upward pressure
of the cresting rotors may be used to operate the upper impeller,
partially or completely. However, once this requirement is
determined, the system can be optimized by extending the ascent channel
capacity (length or number of channels).
Lower impeller: (LIp)
The lower impeller is required to transfer the fallen rotors to the
base of the filled ascent channel. The power requirements
are for the impeller blades to withstand the weight of the water column,
and to fully or partially evacuate a section of the impeller via
compression. This has proven to be the highest power consumption of the
system. However, these power requirements can be
successfully mitigated via a number of methods.
A primary method is replacement, in that as rotors are introduced a
directly related quantity of fluid escapes to the sump system. If the
pressure inside of the ascent channel is constant then this action
creates a proportional vacuum at the top of the fluid column, thereby
reducing the power necessary for this impeller. Even in an
open system, the amount of evacuated fluid, tends to proportionally
reduce the power requirement of this component. Even greater
mitigation is achieved from optimizing the power removed from the
falling rotors, so that sufficient force remains in the rotor to
motivate the impeller via impacts.
The greatest mitigation is in the rotors design and composition.
The shape of the rotors can be optimized for fluid insertion, much like
a car can be designed to lower wind resistance. But the choice of
absorbent materials, such as an open-cell foam, will allow the rotors to
be presented to the base of the ascent channel with only their
unsaturated mass Xm. When the rotors are
introduced to the top of the descent channel the rotor has absorbed
quantity Ym of fluid. Therefore, rotors generate
energy with a mass of Xm+Ym, but
only require the energy of mass Xm at the insertion
point. Consequently, the choice of rotor design and
materials can be substantially improve the Po:Pi
ratio. In our prototyping using household sponges, this ratio could be
as high as 2-3:1. We estimate that using optimum materials this
ratio could be as high as 100 to 1.
Sump System: (SSp)
Fluid will collect at several points in the system. The
lower impeller, the upper impeller, and in the descent channel.
This fluid will be trapped in the sump system. The sump system
consists of various strategic channels which can be optimized to
minimize the depth this excess fluid travels, with the consequent
increase in the sump power requirements. This can be achieved by
returning as much fluid as feasible directly to the top of the ascent
channel during upper impeller operation. However, given that all
evacuated fluid is trapped in the lowest level, which is the case with a
simple design, the sump power requirements remain minimal. This is
because hydrostatic pressure, or siphon action is employed, albeit
augmented. A channel is established from the sump system to
a siphon well in the ascent channel which is lower than the sump
collection point.
The power formula for the system is; Np =
Gp - (SSp + LIp + UIp) |
|